Resources: Fire Pump Overview
This document is
provided for information purposes only. It is not intended to be a
substitute for individual legal counsel or advice on issues discussed
within. Readers seeking resolution of specific legal issues or business
concerns related to the captioned topic should consult their attorney and/or
insurance representative.
Introduction
A fire pump is an integral component of a
total fire protection system. A fire protection system at a facility may
include automatic sprinkler systems, standpipes, hose stations, and/or fire
hydrants.
The purpose of a fire pump is to provide or
enhance the water supply pressure from public mains, suction tanks,
gravity/elevated tanks, lakes, and other bodies of water.
Listed and Approved
The pump, driver, controller, and auxiliary
equipment should be U.L. Listed (Underwriters Laboratories) and/or F.M.
Approved (Factory Mutual) to ensure that the equipment has been thoroughly
examined and appropriately tested for fire pump installations.
NFPA
20,
Standard for the Installation of Centrifugal Fire Pumps requires the
use of listed equipment, or approved equipment, or both. Under the testing
and listing approval system, the manufacturer is responsible for providing a
listed or approved pump that will perform satisfactorily when installed in
conformance with NFPA
20.
Individuals responsible for installing the pump and auxiliary
equipment must also follow the provisions of NFPA
20.
Types and
Characteristics
The two most common types of fire pumps are
the horizontal-shaft centrifugal pump and the vertical-shaft
turbine pump. The horizontal shaft centrifugal pump is one in which the
pressure is developed by impelling water outward from a center of rotation.
The impeller is mounted on a horizontal shaft. The vertical shaft
centrifugal pump is similar, but the impeller is mounted on a vertical
shaft.
These pumps can be driven by electric motor,
internal combustion engines, or steam turbine. Fire pumps are available
with rated capacities from
25
to
5,000
gallons per minute (gpm). Pressure ratings range from
40
to
394
pounds per square inch (psi) for horizontal pumps and
26
to
510
psi for vertical-shaft turbine pumps. Note that natural gas, L-P Gas, or
gasoline engines are not recognized by NFPA
20.
Horizontal-shaft centrifugal fire pumps are
required to be installed to operate under positive suction head (e.g.,
municipal water supply). For new installations, NFPA
20
no longer allows the use of horizontal centrifugal fire pumps taking suction
under lift (e.g., from a pond, reservoir, lake, etc.). If the water supply
is such that suction lift cannot be avoided, a vertical-shaft turbine fire
pump should be installed.
Fire pump design characteristics provide
maximum reliability and specific head-discharge in psi (pounds per square
inch). Fire pumps are designed to provide their rated capacity with a
built-in safety factor (150
percent of rated capacity at
65
percent of rated pressure) to provide a cushion in the event that there is a
greater than expected demand at the time of a fire.
Auxiliary Equipment
Fire pump accessories have an important
bearing on the complete functioning of a fire pump. An understanding of the
following auxiliary equipment is worthy of attention.
A motor controller is a critical
component to ensure the successful operation of the pump. The controller
includes timers, disconnecting means, circuit breakers, and similar devices.
The power supply to the fire pump
should be positioned upstream from the facility’s main electrical
disconnect. In the event of a fire, this will allow the fire pump to
continue to run, even though the power to the facility has been disconnected
(e.g., standard operating procedures for the fire department may be to
disconnect the main power supply to minimize the danger of electrical shock
to fire department personnel). All electrical wiring should be in accordance
with NFPA
70,
National Electrical Code.
Circulation relief valves
are used to prevent the pump from
overheating. Their function is to open at slightly above-rated pressure
when there is little or no discharge, so that sufficient water is
discharged. These valves are not needed on diesel pumps where cooling water
is taken from the pump discharge.
Relief valves
are required on the discharge line when the
operation of the pump can result in excess pressure.
Jockey pumps
maintain pressure in the underground, compensate for leakage, and reduce the
number of times the fire pump starts. Jockey pumps are not needed on
all fire pump installations; however, they are usually found were there is
an extensive underground piping system. They are equipped with gauges,
control valves, and a check valve.
Hose valves
are used in testing pumps.
2 1/2”
valves are attached to a manifold placed outside the pump room to avoid any
damage to the pump, driver, and controller.
Pump Room
Pump rooms and power facilities should be as
free as possible from exposure to fire, explosion, flood, and windstorm
damage. Light, heat, ventilation, and floor drainage should be provided for
pump rooms. Pumps should be located in fire resistive or non-combustible
buildings. A dry location above grade is recommended. Pump rooms should be
large enough to accommodate personnel as well as all equipment and devices
for inspection, maintenance, and testing.
Flushing and
Hydrostatic Tests
New fire pump installations require the
suction piping to be flushed at designated flow rates or at
the hydraulically calculated demand rate of the system, whichever is
greater. The designated flow rates are dependent upon the size of the
suction pipe. (Refer to the following table.)
Pipe Size (Inches) |
4 |
5 |
6 |
8 |
10 |
12 |
Flow (GPM) |
390 |
620 |
880 |
1560 |
2440 |
3520 |
Suction and discharge piping should be
hydrostatically tested at not less than
200
psi pressure, or at
50
psi in excess of the maximum pressure to be maintained in the system,
whichever is greater. The pressure should be maintained for two hours.
Field Acceptance
Tests
Field acceptance tests are required when a
new fire pump has been installed. This test procedure ensures that the
pump, driver, controller, and auxiliary equipment has been properly
installed and is operating per the manufacturer’s specifications. The pump
manufacturer or a representative should be present during the field
acceptance test.
Inspection,
Maintenance, and Testing
The building owner or a representative
(e.g., management company) is responsible for the maintenance of the fire
pump. Fire pumps should be inspected, maintained, and tested per the
manufacturer’s specifications. If the manufacturer’s specifications are
unavailable, refer to the standard for the maintenance of fire pumps NFPA
25
(Standard for the Inspection, Testing, and Maintenance of Water-Based Fire
Protection Systems) or The
Hartford’s Automatic Sprinkler Systems Inspection, Maintenance, and
Testing Procedures Guide.
A comprehensive maintenance program is
generally broken down into three components: inspection, maintenance, and
testing.
Inspection.
A visual examination of the fire pump to
verify that it appears to be in operating condition and is free of physical
damage. Examples include:
-
Heat in pump room is minimum
40
degrees F (70
degrees F for diesel engines)
-
Pump suction, discharge, and
bypass valves are open.
-
Controller pilot light (power
on) is illuminated.
Maintenance.
The work that is performed on the fire pump to make repairs or to keep it
operable. Examples include:
Testing.
A procedure used to determine the status of the fire pump and auxiliary
equipment by conducting periodic physical checks. Examples include:
-
Conduct a weekly churn test
(run pump without water flowing)
-
Conduct an annual full-flow
performance test
-
Operate alarm, supervisory,
and trouble signals
-
Analyze Inspection,
Maintenance, and Test Results
The building owner or a representative
should analyze inspection, maintenance, and test results to ensure that the
fire pump and auxiliary equipment is working properly. Where the results
have identified deficiencies, steps should be immediately taken to correct
the problem(s). This important step is often overlooked, potentially
leaving fire pumps inoperable. Be sure to include this step in the overall
fire pump maintenance program.
What to Do When a
Pump Doesn’t Operate Properly
Measures should be taken during an
impairment to ensure that increased risks are minimized and that the
duration of the impairment is limited. NFPA
20
provides a trouble-shooting checklist to help in identifying causes of pump
problems. Qualified personnel must make the necessary repairs and
adjustments to ensure proper pump operation.
If the pump output is so
deficient that it will not properly supply the required water pressure for
the total fire protection system, an appropriate Impairment Program (e.g.,
notify the fire department, institute a fire watch, discontinue hazardous
operations, etc.) should be incorporated, and repairs should be completed as
quickly as possible.
Conclusion
Understanding the proper selection,
installation, and maintenance of a fire pump can make the difference between
business as usual and a catastrophe at a facility.
Ensure that:
-
(1)
a pump, driver, controller,
and auxiliary equipment is U.L. Listed or F.M. Approved
-
(2)
the appropriate type of pump
and auxiliary equipment is selected and properly installed
-
(3)
the pump room and power
facility is free from fire, explosion, flood, and windstorm damage
-
(4)
for new installations,
flushing, hydrostatic and field acceptance tests have been conducted
-
(5)
a comprehensive inspection,
maintenance, and testing schedule has been incorporated in the facilities
overall preventive maintenance program.
-
References
-
1.
AISG Fire Protection Bulletin, “Fire Pump Maintenance,” Number
43.04
-
2.
The Hartford, Automatic
Sprinkler Systems, Inspection, Maintenance, and Testing Procedures Guide
-
3.
NFPA
20,
Standard for the Installation of Centrifugal Fire Pumps
-
4.
NFPA
25
Standard for the Inspection, Testing, and Maintenance of Water-Based Fire
Protection Systems
-
5.
NFPA Fire Protection Handbook,
18th
Edition, Section
6,
Chapter
4.
-
This document is
provided for information purposes only. It is not intended to be a
substitute for individual legal counsel or advice on issues discussed
within. Readers seeking resolution of specific legal issues or business
concerns related to the captioned topic should consult their attorney and/or
insurance representative.
Licensed
• Insured • Professional
|